Freelance 800F系统可以由
许多连接I/O单元的过程控制站组成。您可以选择这
些过程站为冗余模式(CPU冗余,现场总线模块冗
余)或非冗余模式。模块化的可插拔式输入/输出模
块依照系统过程信号的类型和数量自由选择使用。
AC800F控制器通过现场总线连接远程I/O或现场设
备。
系统通讯
操作员级和过程控制级之间通信使用TCP/IP
协议系统总线(基于以太网),您可以选择不同
的传输介质例如AUI、双绞线、光纤或同轴电缆。
Freelance OPC服务器用于连接更高-级的操作员
站(800xA) 或其他OPC客户端。Freelance控制 系
统中的实时过程值和报警可以通过OPC进行访问。
我们同时提供一个C语言编程接口嵌入到外部基于
Windows操作系统应用程序中,适用于实现用户使
用非标准OPC通信,即DMS-API 软件包。
项目数据库
所有配置的信号

VMIVME-5565
Industrial” DCS system design purpose: the most economical engineering investment, the most powerful control function.
Five features of Industria1″ DCS system:
1. All-round integrated control system, integrating DCS & PLC & Field Bus;
2. Using RISC SuperScalar high-speed CPU, with super performance;
Three high reliability, strict industrial application practice, more than 1000 sets of application performance in China;
4. It has good openness, flexibility and scalability;
Fifth, the project is easy, the interface is friendly, and the maintenance is simple;
2. Industria1″ system communication
Industrial” system uses international standard industrial bus. Field controller supports Profibus, FF, ModBus, Can, etc.
International standard fieldbus, Profibus is the most widely used open fieldbus international standard in the world, divided into FMS, DP and PA
Level 3, DP communication rate can be as high as 12Mb. Profibus is used to connect intelligent devices such as distributed I/0 stations and field bus instruments.
Communication between the process station, operator station and engineering station takes place via the system bus DigiNetS (Industrial Ethernet). user
Different transmission media (RJ45 twisted pair, thin, thick or fiber optic cables and mixed media) and network topology can be selected for the system bus.
Simple layout, due to the use of TCP/IP protocol, the system can also use the public telephone network (dial-up mode) or satellite to achieve ultra-long-distance communication.
Subsystems such as PLC communicate with the Industrial” system through the ModBus protocol interface. The system also supports IEC870-5 over-control protocol.
discussion.
The Flash EPROM inside the PS provides more than 220 functional modules (control algorithm subroutines), in addition to the basic ones specified in the IEC 61131 3 standard
In addition to this content, many powerful and rigorously tested function blocks from actual engineering applications have been expanded. any complex control
The scheme can be realized by the combination of these function blocks.
The function blocks provided by the system mainly include the following categories:
o
Analog processing
o
digital processing
loop regulation
Logical sequence control
c
logic operation
Monitoring function
Collection function.
c
arithmetic operations
c
TCP/IP protocol communication interface
Modbus protocol communication interface
1EC870-5 protocol communication interface (Telecontrol)
4.2 Field Controller PS
Industrial” field controller PS is a special process control station, which is embedded with field bus communication interface for users to use
Fieldbus technology offers very flexible options. Each PS allows to insert 4 fieldbus interface cards (the card type can be different),
Each card is connected to 1 field bus to collect process data and diagnostic information from the bus, the interface card is easy to replace and plug and play
(Plug & Play), and can be plugged and unplugged.
The field controller PS has the following characteristics:
o
Flexible: supports all international standard open fieldbuses and can be mixed
Simultaneous connection of 4 high-speed fieldbuses (max. 12 MBd)
Simple engineering: configuration, commissioning and diagnostics using only the same tool CBF (Control Build F) software
mouth
Access to all information from the field including equipment management information
Global database of fieldbus devices, control levels and HMI (Human Machine Interface) usage systems
Module identification with production operating parameters
c
complete self-diagnosis
Compact and robust design
Front Panel Wiring
DIN rail (U-shaped) installation well can be directly wall mounted, simple and convenient
o
Allowable operating ambient temperature…60 C, with automatic temperature monitoring
o
EMC (Electromagnetic Compatibility) according to EN50082
mouth
Certifications: CE, NAMUR, CSA, CSA-NRT